2020 Atlas Copco QAS Generators 250 JD

2020 Atlas Copco QAS Generators 250 JD

Swipe to View More

  • Year 2020
  • Make Atlas Copco
  • Model QAS Generators
  • Engine John Deere 6090HFG06
2020 Atlas Copco QAS Generators 250 JD

2020 Atlas Copco QAS Generators 250 JD

2020 Atlas Copco QAS Generators 250 JD

Mobile diesel generators

The QAS range, from 25 to 625 kVA

Features may include:

Up to 20 MVA stable power
  • 32 units of the QAS 625 can be linked together in paralleling for specialized applications, providing up to 20MVA of stable and reliable power.
Corrosion resistant canopy
  • 1000 hour salt test
Double runtime
  • Up to 40-hour fuel tank capacity provides longer runtime between fill ups and optimum site autonomy.
Stable power in less than 6 seconds
  • The starting mechanism ensures that stable power is achieved in less than six seconds.
Engines Tier 4F
  • All QAS generators include the latest Tier 4 Final engine
Dirt and dust. No problem!
  • All QAS generators have dual stage filtration with a safety cartridge and dual stage air cleaning. This centrifugal dust separation system and heavy duty filtration system prolongs the life of your generator.
QAS generators
  • The ideal mobile diesel generator solution for rental companies
  • The QAS generator range was designed specifically for the needs of the US market. The range has been completely overhauled and incorporates nine models covering power rating from 25 to 625 kVA. All QAS generators include the latest Tier 4 Final engine and have a footprint that is up to 20 per cent smaller than the previous generation. The starting mechanism ensures that stable power is achieved in less than six seconds.
  • The range is all about the user experience and maintaining the value of your asset. It’s packed with features that make operating, transporting and maintenance as easy as possible.
  • What is more, up to 32 units of the QAS 625 can be linked together in paralleling for specialized applications, providing up to 20MVA of stable and reliable power.
Make the Perfect Power
  • When you need power, maybe a single generator is not always the most efficient solution. Does the application load vary? Do you need prime power for long term projects on a remote site? Do you need a semi-permanent installation that can be upgraded or downgraded?
  • A Modular Power Plant (or paralleling multiple generators) is the efficient solution if you answered yes to any of the above questions. Simply, this is a configuration of generators working together.
  • We have developed a unique Power Management System (PMS). The PMS system enables the optimization of fuel consumption and expands the generator’s lifetime. PMS manages the quantity of generators running in parallel with load demand, starting and stopping units in line with increases or decreases in load. In this way, the load on each generator remains at a level which optimizes fuel consumption. It also eliminates the need for generators to run with low load levels, which can cause engine damage and shorten the life expectancy of the equipment.
Power Management System
  • The generators incorporate Atlas Copco’s Power Management System (PMS) that manages the quantity of generators running in parallel with load demand, starting and stopping units in line with increases or decreases in load. In this way, the load on each generator remains at a level which optimizes fuel consumption and eliminates the need to run with low load levels, which can cause engine damage and shorten the life expectancy of the equipment.

Engine

Engine John Deere 6090HFG06
Engine Power Continuous Output: 334 hp (249 kW) | Gross Output: 366 hp (273 kW)
Rated Engine Speed 1800 rpm
Displacement 9 L
Cylinder Liners 6
Aspiration Turbo w/Intercooler
Emissions US EPA Family: KJDXL09.0313 | US EPA Tier: Tier 4 Final

Battery

Battery Capacity, Maximum 1100 x2 A

Electric

Electrical Frequency: 60 Hz | Rated prime power 3ø: 200 kW (250 kVA) / Standby: 250 kW (275 kVA) | 3ø Voltage in 480V switch position (series star w/neutral): 480Y / 277 V | Amp capacity @480V: 301 A | 3ø Voltage in 240-208V switch position (parallel star w/neutral): 240YY / 139 - 208YY V | Automatic voltage regulator (+/-0.5%): Leroy Somer R450 | Electrical system (Negative ground): 24 V | Amp capacity @240V: 600 A / 600 A | Amp capacity @208V: 132 A | 1ø Voltage in 120-240V switch position (Zig-Zag): 240 / 120 V | Amp Capacity @120V: 600 x2 | Main breaker - Shunt trip: 800 A | 3ø Power factor: 0.8 | 1ø Power factor: 1.0 | Rated prime power 1ø: 83 kW (83 kVA)
Alternator Leroy Somer 46.2 L6 | Engine output: 60 A

Operational

Operating Conditions Fuel consumption at full load (PRP): 14.2 gal / h (53.8 l/h) | Fuel autonomy considering 90% of fuel capacity: 34 h
Operating Temperature, Maximum Ambient (@Sea Level): 122 ºF | Min. starting: 14 ºF

Performance

Noise Level Max. sound pressure(LPA) @23' @75% Load: 73 dB(A)

Dimensions

Length w/ Trailer: 158 in | Skid: 218in
Width w/ Trailer: 55 in | Skid: 94 in
Height w/ Trailer: 93 in | Skid: 109 in

Capacities

Cooling System Engine: 13.6 gal
Fuel Capacity Tank: 385 gal (1457 l)
Oil capacity Engine: 10.6 gal

Weights

Weight w/ Trailer wet: 11870 lbs | Skid wet: 14175 lbs

Features

Features Excitation: AREP | Insulation: Class H | Power distribution - Terminal board: 5 Wire (L1, L2, L3, N, Ground) | Terminal board connections: Bare wire Terminals | Maximum terminal cable size: 350MCM

Product Photography